DATE: June 2, 2003
FROM: Cheryl A. Fischer, P.E.
Asst. Dir. for Code Interpretation
NOTE: Fire separation requirements
between a motor vehicle repair shop and the sales office
This is in response to your
questions regarding the fire separation requirements between a motor vehicle
repair shop, S-1 occupancy and the sales office, B occupancy.
Building Code of New York State
(BCNYS) section 406.6, Repair garages, is applicable as follows:
Section 406.6.2, Mixed occupancy, provides that a repair garage shall
not be located within, or attached to, a building occupied for any other
purpose, unless separated from the other occupancies as prescribed in
section 302.3.3. Such separation shall be continuous and unpierced, except
for doors leading to salesrooms, or offices, operated in connection with
such garages, and provided such openings are equipped with self-closing
fire doors conforming to the requirements of Chapter 7. Section 302.3.3,
Separated uses, refers to Table 302.3.3, which requires a three (3) hour
fire separation between the garage and the office. Footnote b, applicable
to the B occupancy states that:
Occupancy separation need not be provided for incidental storage areas
within Groups B and M if the:
1. Area is less than 10 percent of the floor area, or
2. Area is provided with an automatic fire-extinguishing system and is
less than 3,000 square feet, or
3. Area is less than 1,000 square feet.
Please note that section 406.6
is applicable in its entirety.
This advisory opinion is rendered
based upon the information provided. Administration and enforcement of
the code are within the jurisdiction of the local authority. If you have
questions regarding this advisory, please call me at (518) 474-4073.
Al03-128