DATE: June 5, 2003

FROM: Cheryl A. Fischer, P.E.
Asst. Dir. for Code Interpretation

NOTE: Certificate of Acceptability: CA 0009
G-P Gypsum Series 600(NY), Gyproc 2-Hour Area Separation Wall Solid Type

This is in response to your question regarding the installation of the ½" gypsum over the gypsum and H-Stud and C track assembly. Specifically you ask if the joints of the gypsum have to be over the H-Studs.
Yes.

Section 4.3.3, Field Erection, states in part: ... On each side, a layer of ½" Fireguard C gypsum board is screwed to the H-Studs and C Track with 1" type S screws 12" o.c.

The section requires the gypsum to be screwed to the H-Studs. The joints at the panel ends have to be screwed to the H-Studs for stability.